To obtain a copy of building/electrical/mechanical/energy-code amendments,
please call 240 777-6370. For fire-code amendments, call 240 777-2457.
Local amendments, where listed, are available in Adobe PDF format. For information on building codes and standards in effect for previous years,
click here.
|
TYPE
|
CODE/EDITION
|
LOCAL AMENDMENTS
|
EFFECTIVE DATE
|
|
Yes
|
No
|
|
Commercial Building Code
|
ICC International
Building Code/2006
|
X
|
|
05-13-2008
|
|
MBRC Maryland Building Rehabilitation Code
|
|
X
|
07-16-2007
|
|
Residential Building, Energy & Mechanical Code
|
ICC International Residential Code/2006
|
X
|
|
05-13-2008
|
|
MBRC Maryland Building Rehabilitation Code
|
|
X
|
07-16-2007
|
|
Electrical Code
|
NFPA National Electrical Code/2002
|
X
|
|
04-01-2005
|
|
Commercial Mechanical Code
|
ICC International Mechanical Code/2006
ICC International Fuel Gas Code/2006
|
X
|
|
05-13-2008
|
|
Plumbing & Gas Code
|
WSSC Plumbing Code
|
|
X
|
05-01-2007
|
|
Life-Safety Code
|
NFPA-101/2003
|
X
|
|
11-28-2006
|
|
Fire Alarm Code
|
NFPA-72/2002
|
X
|
|
11-28-2006
|
|
Sprinkler Code
|
NFPA-13/2002
|
X
|
|
11-28-2006
|
|
Residential Sprinkler
|
NFPA-13D & 13R/2002
|
X
|
|
11-28-2006
|
|
Accessibility
|
COMAR
05.02.02, ADAAG & FFHAG
|
|
X
|
02-01-1995
|
|
Energy Conservation (Commercial Buildings)
|
ICC International Energy Conservation Code/2006
|
X
|
|
05-13-2008
|
*MBRC applies to a building or structure that was erected and occupied or issued a certificate of occupancy at least 1 year before a construction permit application for that building or structure was made to a local jurisdiction.
Residential Construction Design Parameters |
|
Ground Snow Load
|
Wind Speed |
Seismic Design Category
|
Subject To Damage From |
Wea- thering |
Frost Line Depth |
Termite |
Decay |
|
30 PSF
(1.4 kN/m²)
|
90 mph
(145 km/hr)
|
B
|
Severe |
24 in (610 mm) |
Moderate to heavy
|
Slight to moderate
|
(Continued) |
Winter Design Temp. |
Ice Shield Underlayment Required |
Flood Hazards
|
Air Freezing Index |
Mean Annual Temp. |
|
13°F(-10.6°C)
|
Yes |
July 2, 1979 |
300 |
55°F(12.8°C) |
Commercial Construction Design Parameters |
Ground Snow Load |
Wind Speed |
Spectral Response Acceleration
|
Wea- thering
|
Frost Line Depth |
|
Ss %g
|
S1 %g
|
|
30 PSF
(1.4 kN/m²)
|
90 mph
(145 km/hr)
|
16
|
5.1
|
Severe |
24 in
(610 mm)
|
Last edited: 5/13/2009
|
|
GENERAL
Help
Sign In
Search DPS
About DPS
What's New?
General
eDocuments
Clarksburg
Customer Satisfaction Survey
Search Building Contractors
PERMITTING
Bldg. Const.
Inspections
Licenses
Roads
Site Plan Enforcement
Water Res.
Well & Septic
Zoning
CONTACT US
Address
Directions
Submit Online
Complaint
Phone List
Email DPS
|